Request Price |
| Output Ratings: |
| Standby |
Prime |
60 HZ, 350 KW, 438 KVA
50 HZ, 310 KW, 388 KVA |
315 KW, 394 KVA
282 KW, 353 KVA |
|

|
|
|
- Engine:
Cummins 4 cycle 6 Cylinder Turbocharged in line
|
- Main Alternator:
Self regulating, screen protected and drip proof. 12 lead reconnectable to:
208/120, 220/127, 230/115, 380/220, 415/240, 480/277 Manufactured by Newage
Full load current at 220 Volts, 60 HZ, .8 PF 1150 Amps.
Full load current at 220 Volts, 50 HZ, .8 PF 1019 Amps
|
|
|
- Cooling System:
Rail mounted radiator, high ambient 120 °F
|
- Electrical System:
Safety shutdown in event of low oil pressure or high engine temperature.
24 Volt Battery Charging Alternator.
|
- Fuel Consumption:
Full load 60 Hz, 1800 RPM 24.4 GPH [92 L/HR]
Full load 50 Hz, 1500 RPM 21.6 GPH [82 L/HR]
|
- Instrument Panel:
| Set mounted key start panel in a vibration isolated
sheet metal enclosure with a hinged door. The control panel is equiped as follows:
|
- AC Voltmeter
- AC Ammeter
- Frequency Meter
- Volt/Amp Phase Selector Switch
- Running Time Meter
|
- Coolant Temperature Gauge
- Oil Pressure Gauge
- Battery Condition Meter
- Start/Stop Key Switch
- Oil Pressure Bypass Switch for Startup
|
|
- Documentation & Warranty:
Wiring diagram, engine manual, main alternator manual.